sinee — 7.14 F13 Group: Torque Control Parameter

EM500 Open-Loop Vector Control Inverter User Manual F13.01=0: Numeric Torque Setting F13.02 The torque is set through F13.02. F13.01=1: AI1 F13.01=2: AI2 F13.01=3: AI3 F13.01=4: AI4 (Expansion Card) The torque is controlled by AI (percentage) * F13.02. F13.01=5: High-Frequency Pulse Input (X7) The torque is controlled by HDI (percentage) * F13.02. Please refer to the description of F00.04 for detailed explanations of AI1-AI4 and X7. F00.04 has the same meanings as AI1-AI4 and X7. 100.00% is the percentage inputted through F13.02 (Numeric Torque Setting). F13.01=6:

Communication Percentage Setting The torque is determined by communication, etc  If inverter is under master-slave communication control (F10.05=1) and present inverter is a slave (F10.06=0), the set percentage is “700FH (Master-Slave Communication Setting) * F10.08 (Receiving Proportionality Factor of Slave)”.  For general communication (F10.05=0), the set percentage is “7003H (Torque The range of 700FH is -100.00% to 100.00%. See Table 12-2 for details. Communication Setting) * F00.18 (Numeric Torque Setting)”. The range of 7003H is -200.00% to 200.00%. See Table 12-2 for details 274 3: AI3 4: AI4 (Expansion Card) 5: High-Frequency Pulse Input (X7) 6:

Communication Percentage Setting (Full ranges of options 1 to 6, correspond to numeric torque setting F13.02) 7: Not Used 8: digital potentiometer F13.02 Numeric Torque Setting -200.0 - 200.0 (100.0= Motor Rated Torque) % 100.0 ●