EM500 Open-Loop Vector Control Inverter User Manual 100.00%. Details are shown at table 12-2. For general communication (F10.05=0) * F13.09 (upper limit frequency) F13.08=6, the upper limit frequency is 700BH (Communication Percentage Setting) F13.08=7, the upper limit frequency is 7018H (Communication Setting) The range of 700BH is 0.00% to 200.00%. The range of 7018H is 0.00 to F00.16 (maximum frequency). maximum frequency of the inverter.
The upper limit frequency of torque control mode is used to set forward or reverse For torque control mode if the load torque is less than the motor output torque, the motor speed will continue to rise, to prevent mechanical systems appear coasters and other accidents, must limit the highest motor speed; Even if the load is greater than the motor output torque and the motor will be reversed. If F13.19 is set to 1 motor run highest load frequency is still limited, if F13.19 is set to 0 means that the highest motor running load frequency is not restricted. The reverse upper limit frequency is decided by F13.09 * F13.18. input by AI1 analog quantity:
When the AI1 analog quantity input is positive, the forward For example, Torque reference is positive, torque control upper limit frequency is speed amplitude limiting upper limit frequency value is AI1 (percentage) * F13.09, The reverse speed amplitude limiting upper limit frequency value is AI1 (percentage) * F13.09*F13.18; When the AI1 analog quantity input is negative, the forward speed amplitude limiting upper limit frequency value is AI1 (percentage) * F13.09*F13.18 The reverse speed amplitude limiting upper limit frequency value is AI1 (percentage) * F13.09.
Torque control maximum operating frequency = torque control upper limit frequency + upper limit frequency offset (only F13.08 = 1 ~ 5 effective), but the maximum operating frequency by F00.16 maximum frequency limit 277 No. Function Range Unit Default Type F13.11 Static Friction Torque Compensation 0.0 - 100.0 % 0.0 ●