EM500 Open-Loop Vector Control Inverter User Manual In driving an object, motor must overcome the static/kinetic friction. Setting this group of parameters can enable the torque to rotate as per the specified torque after having overcome the inherent static/kinetic friction force. The static friction prevails before motor runs, but the kinetic friction prevails after motor runs. All in all, this group of parameters is related to motor capacity performance. When the actual frequency (estimated frequency if inverter is in the SVC control mode) is less than or equal to the value set through F13.12, then the output torque is “set frequency + F13.11 Static Friction Torque Compensation”.
When the actual frequency is greater than the value set through F13.12, the output torque is “Set Torque + F13.13 Kinetic Friction Torque Compensation”. The greater the compensation is, the higher the compensation level will be. The percentage of the compensation is equal to the torque setting percentage. 7.15 F14 Group: Motor 2 Parameter EM500 inverter can be switched between two motors. User may perform motor nameplate parameter settings, motor parameter tuning, the selection of VF control or vector control, related parameters of the encoder, and parameters related to VF control or vector control performance for these two motors respectively.
Motor parameters of the second group are listed in F14, with the function codes having the same meanings as that of the first group.F14.00 - F14.34 correspond to F01.00 - F01.34 and they are respectively motor nameplate parameter, motor parameter, encoder 278 F13.12 Static Friction Compensation Frequency Range 0.00 - 50.00 Hz 1.00 ● F13.13 Kinetic Friction Torque Compensation 0.0 - 100.0 % 0.0 ● F13.14 ~ F13.17 Not Used