sinee — 7.16 F15 Group: Auxiliary Function

EM500 Open-Loop Vector Control Inverter User Manual parameter, etc.; F14.35 corresponds to F00.01, for motor control mode; F14.36 - F14.76 corresponds to F06.00 - F06.40, as vector control parameters; F14.77 refers to the acceleration/deceleration options for motor 2. In the following, only F14.72 is described. For the other parameters, please refer to the descriptions of relevant parameter of Motor 1. F14.77 =0 , the acceleration/deceleration time of motor 2 is the same as that of motor 1.

Refer to descriptions of F15.03 - F15.09 F14.72=1/2/3/4 , the acceleration/deceleration time of motor 2 is fixed as the acceleration/deceleration time 1, 2, 3 and 4, which correspond to F00.14 - F00.15/F15.03 - F15.04/F15.05 - F15.06/F15.07 - F15.08 respectively 7.16 F15 Group: Auxiliary Function As indicated in Figure 7-32, if FJOG/RJOG is enabled, inverter will start running at the frequency set through F15.00; after it is disabled, inverter will stop as per the stop mode. 279 No. Function Range Unit Default Type F14.77 Motor 2 Acceleration/Deceleration Time 0: Same as Motor 1 1: Acceleration/Deceleration Time 1 2: Acceleration/Deceleration Time 2 3: Acceleration/Deceleration Time 3 4:

Acceleration/Deceleration Time 4 0 〇 No. Function Range Unit Default Type F15.00 JOG Frequency 0.00 - Maximum Frequency F00.16 Hz 5.00 ● F15.01 JOG Acceleration Time 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 5.00 ● F15.02 JOG Deceleration Time 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 5.00 ●