sinee — 7.16 F15 Group: Auxiliary Function

EM500 Open-Loop Vector Control Inverter User Manual When inverter is running, F15.01 and F15.02 are set as acceleration and deceleration time. However, the set values (for example 500) have different meanings and ranges, depending upon the time unit (F15.13). If F15.13=0, it means that the acceleration/deceleration time is 5.00s; if F15.13=1, it means that the acceleration/deceleration time is 50.0s.

Output Frequency Acceleration/ Deceleration Time Reference Frequency F15.09 Jog Frequency Jog Running Disabled F15.00 t 0 Actual Acceleration Time Actual Deceleration Time Jog Acceleration Jog Deceleration Time F15.01 Time F15.02 ★ :JOG running mode, user may independently set frequency and Figure 7-32 Jog Running acceleration/deceleration time, which shall not be shared but not having the same physical meaning with normal running The trigger conditions for JOG running command depend upon inverter control Table 7-20 JOG Running Command modes. See Table 7-20 for details. 280 y Jog Run ning Enabled Command Source JOG Running Command Options (F00.02) 0:

Keypad Control M.K (F12.00) can be set as “1: FJOG” or “2: RJOG”. Press M.K , then JOG running command is enabled; release M.K , then JOG running command is disabled. ★ Remove the keypad during JOG running to stop inverter 1: Terminal Control Numeric input terminal function “4: FJOG” or “5: RJOG”. Under default conditions, if the function terminal is enabled, JOG running command is active; if the function terminal is disabled, JOG running command is inactive.