EM500 Open-Loop Vector Control Inverter User Manual acceleration/deceleration time options (first group F00.14 and F00.15) to meet different As for normal running (non jog running), the system offers 4 groups of demands. After setting, user may switch between the numeric input mode “19: Acceleration/Deceleration Time Terminal 1” and “20: Acceleration/Deceleration Time Terminal 2”. See Table 7–4 Numeric Multi-Function Input Terminals” 281 2: Communication Control If host controller writes “0003H: FJOG” or “0004: RJOG” in the register 7000H through MODBUS protocol, JOG running command will be active; writes “0007H: coast to stop”, JOG running command will be inactive. No.
Function Range Unit Default Type F15.03 Acceleration Time 2 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.04 Deceleration Time 2 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.05 Acceleration Time 3 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.06 Deceleration Time 3 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.07 Acceleration Time 4 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.08 Deceleration Time 4 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.09 Acceleration/Deceleration Time Reference Frequency 0:
Maximum Frequency F00.16 1: 50.00Hz 0 〇