EM500 Open-Loop Vector Control Inverter User Manual Output Frequency Acceleration/ Deceleration Time Reference Frequency F15.09 Set Frequency 0 Actual Acceleration Time Actual Deceleration Time t Set Deceleration Time Set Acceleration Time Figure 7-33 Acceleration/Deceleration Time As indicated in Figure 7-33, the defined acceleration time refers to the time that the frequency increases from 0.00 Hz to the acceleration/deceleration time reference frequency; the deceleration time refers to the time that the frequency decreases from the acceleration/deceleration time reference frequency to 0.00 Hz.
Actual acceleration/deceleration time depends upon the ratio of the set frequency to the reference frequency. F15.09=0, the reference frequency is set by F00.16 (maximum frequency). If also F15.09 is used to set the acceleration/deceleration time reference frequency. If F00.16=100.00 Hz, the acceleration time refers to the time that output frequency increases from 0.00 Hz (100.00 Hz) to 100.00 Hz (0.00 Hz), and the deceleration time refers to the time that output frequency decreases from 100.00 Hz (0.00 Hz) to 0.00 Hz (100.00 Hz) 282 No. Function Range Unit Default Type F15.10 Automatic Switching between Acceleration and Deceleration Time 0: Disabled 1:
Enabled 0 〇 F15.11 Switching Frequency between Acceleration Time 1 and Acceleration Time 2 0.00 - Maximum Frequency F00.16 Hz 0.00 ● F15.12 Switching Frequency between Acceleration Time 1 and Acceleration Time 2 0.00 - Maximum Frequency F00.16 Hz 0.00 ●