sinee — 7.16 F15 Group: Auxiliary Function

EM500 Open-Loop Vector Control Inverter User Manual If inverter runs at a common (other than PLC, PID, etc.) speed (other than torque, etc.) of motor 1 and the acceleration and deceleration time terminals (19: Acceleration/Deceleration Time Terminal 1, 19: Acceleration/Deceleration Time Terminal 1) are disabled, inverter can complete the automatic switching between the two terminals by setting F15.10 as 1. See Figure 7-34 for details.

Output Frequency Switching Frequency between Acceleration Time 1 and Acceleration Time 2 Switching Frequency between Acceleration Time F15.11 1 and Acceleration Time 2 F15.12 0 Acceleration Acceleration Deceleration Deceleration t Time 1 F00.14 Time 2 F13.03 Time 2 F13.04 Time 1 F00.15 Figure 7-34 Automatic Switching between Acceleration Time and Deceleration Time the acceleration time 1 is the preset acceleration time, otherwise, the acceleration time 2 In acceleration, if output frequency is less than the value set through F15.11, then is present acceleration time In deceleration, if output frequency is less than the value set through F15.12, then the deceleration time 1 is the preset deceleration time, otherwise, the deceleration time 2 is present deceleration time.

The acceleration/deceleration time can be a large figure depending upon different working conditions. The system offers 3 kinds of acceleration/deceleration time units, which are set through F15.13. If F15.13=1, it means that the acceleration/deceleration time unit is “0.1 s”. In addition to F13.06 torque control acceleration and deceleration 283 No. Function Range Unit Default Type F15.13 Acceleration/Deceleration Time Unit 0: 0.01s 1: 0.1s 2:1s 0 〇