EM500 Open-Loop Vector Control Inverter User Manual time, all other acceleration and deceleration time will be changed. In default condition, such as the value of F00.14 ,15.00s will change to 150.0s. The hopping frequency function enables inverter output frequency to avoid the mechanical resonance with the mechanical load. Inverter is not permitted to run at a constant speed in the hopping frequency range, but in the acceleration process, there is no hopping and inverter runs smoothly.
Set Frequency Hopping Frequency Point 3 Hopping Range 3 Frequency Frequency Hopping Range Hopping Frequency Frequency Point 2 Hopping 2 Frequency Hopping Range Point 1 1 t Figure 7-35 Frequency Hopping As indicated in Figure 7-35, the frequency hopping function is set through “Hopping Frequency Point+Frequency Hopping Range”. Specific frequency hopping is: Hopping Frequency Point-Frequency Hopping Range, Hopping Frequency Point+Frequency Hopping Range. Up to three frequency hopping ranges can be set. When their hopping ranges are all set as 0, corresponding frequency function is disabled. 284 No.
Function Range Unit Default Type F15.14 Hopping Frequency Point 1 0.00 - 600.00 Hz 600.00 ● F15.15 Frequency Hopping Range 1 0.00 - 20.00, 0.00: Disabled Hz 0.00 ● F15.16 Hopping Frequency Point 12 0.00 - 600.00 Hz 600.00 ● F15.17 Frequency Hopping Range 2 0.00 - 20.00, 0.00: Disabled Hz 0.00 ● F15.18 Hopping Frequency Point 13 0.00 - 600.00 Hz 600.00 ● F15.19 Frequency Hopping Range 3 0.00 - 20.00, 0.00: Disabled Hz 0.00 ●