EM500 Open-Loop Vector Control Inverter User Manual When the frequency hopping function is enabled and if the set frequency is in the frequency hopping range, then the finally set frequency will be “Hopping Frequency Point-Frequency Hopping Range” during the rising of the set frequency or will be “Hopping Frequency Point+Frequency Hopping Range” during the decrease of the set frequency.
Different frequency hopping ranges may be superposed (see the frequency hopping ranges 1 and 2 in Figure 7-35) and the final frequency hopping range is (Hopping Frequency Point 1-Frequency Hopping Range 1, Hopping Frequency Point 2+Frequency Hopping Range 2) Output Frequency Set Frequency + Range Set Frequency Set Frequency – Range 0 t Output Terminal Disable d Disabled 0 t Figure 7-36 FAR Detection As indicated in Figure 7-36, when the multi-function output terminal or relay output is set as “2:
FAR”, if the absolute value of the difference between output frequency and the set input frequency is less than or equal to FAR (F15.20) during inverter running (non-autotuning), the multi-function output terminal outputs active level, otherwise the multi-function output terminal outputs inactive level. 285 No. Function Range Unit Default Type F15.20 FAR Detection Bandwidth 0.00 - 50.00 Hz 2.50 〇 Disabled En Enable d ab