EM500 Open-Loop Vector Control Inverter User Manual Figure 7-37 FDT Detection As indicated in Figure 7-37, when the multi-function output terminal or relay output is set as “3: Output Frequency Detection Range FDT1” or “4:
Output Frequency Detection Range FDT2”, if the absolute value of output frequency is greater than output frequency Detection Range FDT1/2 (F15.21/F15.23), corresponding function terminal outputs active level during inverter running; if the absolute value of output frequency drops to a value less than or equal to “Output Frequency Detection Range FDT1/2 (F15.21/F15.23) - FDT1/2 hysteresis”, corresponding function terminal outputs inactive level; if the absolute value of output frequency falls between “Output Frequency Detection Range - Hysteresis” and “Output Frequency Detection Range”, the output level of corresponding function terminal remains the same. 286 No.
Function Range Unit Default Type F15.21 Output Frequency Detection Range FDT1 0.00 - Maximum Frequency F00.16 Hz 30.00 〇 F15.22 FDT1 Hysteresis -(Fmax-F15.21)~F15.21 Hz 2.00 〇 F15.23 Output Frequency Detection Range FDT2 0.00 - Maximum Frequency F00.16 Hz 20.00 〇 F15.24 FDT2 Hysteresis -(Fmax-F15.23)~F15.23 Hz 2.00 〇