sinee — 7.16 F15 Group: Auxiliary Function

EM500 Open-Loop Vector Control Inverter User Manual The analog level detection can be used to detect and monitor present setting of F15.25 and also for internal operation, external alarm monitoring, etc. Two detection conditions can be set, but the detection is only for one analog input channel. Analog Quantity AI % Detection Level Hysteresis Output 0 t (s) Terminal Disabled Disabled Enabled 0 t (s) Figure 7-38 ADT Detection As indicated in Figure 7-38, the detection level has been set with a valid start point.

When the analog input has been processed for offset and after this, its percentage is greater than the detection level, the function ADT is enabled; if the conditions for “disable” are determined by the monotonic deceasing hysteresis, when the transformation result of the input analog is reduced to a value below “Detected Level - Hysteresis”, the function ADT is disabled 287 No. Function Range Unit Default Type F15.25 Analog Input Level Detection ADT 0: AI1 1: AI2 2: AI3 3:

AI4(Expansion Card) 0 ○ F15.26 Analog Input Level Detection ADT1 0.00 - 100.00 % 20.00 ● F15.27 ADT1 Hysteresis 0.00 - F15.26(Monotonic deceasing is active) % 5.00 ● F15.28 Analog Input Level Detection ADT2 0.00 - 100.00 % 50.00 ● F15.29 ADT2 Hysteresis 0.00 - F15.28(Monotonic deceasing is active) % 5.00 ● No. Function Range Unit Default Type F15.30 Energy 0: Disabled 0 〇