sinee — 7.16 F15 Group: Auxiliary Function

EM500 Open-Loop Vector Control Inverter User Manual the control mode can be set through F15.33 When the set frequency of inverter is lower than the lower limit frequency (F00.19), through F15.34See Table 7-21 for control modes of fan Three fan control modes are available to reasonably use the fan. It is controlled Table 7-21 Fan Running ★ If “2: Run at Intelligent Temperature Control” is selected, make sure that inverter temperature detection module works normally. increase the over modulation intensity to enhance the utilization factor of bus voltage and When the input voltage of inverter is lower than its output frequency, user may increase the upper limit of output voltage.

If F15.35=1.10, the upper limit of the voltage may be increased by up to 10%, output current at load may be reduced, but the current harmonic will go up 289 No. Function Range Unit Default Type F15.33 Control Mode of Set Frequency Lower Than Lower Limit Frequency 0: Run at Lower Limit Frequency 1: Stop 0 〇 No. Function Range Unit Default Type F15.34 Fan Control 0: Run at Energization 1: Run at Star 2: Run at Intelligent Temperature Control 1 〇 Fan Control Description 0: Run at Energization Fan runs immediately after inverter is powered on. 1: Run at Star Fan starts running after inverter starts running; fan stops running 1 minute after inverter enters the parameter setting status. 2:

Run at Intelligent Temperature Controll When inverter temperature > 45℃, fan starts running; when inverter temperature No. Function Range Unit Default Type F15.35 Over modulation Intensity 1.00 - 1.10 1.05 ●