EM500 Open-Loop Vector Control Inverter User Manual This function code refers to the setting of the acceleration/deceleration time while inverter is in “rapid stop”. F15.44=0 Start Using Start phase sequence phase detection function F15.44=1 Shut Down Closed phase sequence phase detection function 1. Phase sequence phase detection function is valid only for the synchronous machine, and it must be equipped with phase sequence phase detection card can be used. F15.45=0 Automatic switch When the specified phase angle difference is reached, the inverter will automatically switch over.
Switching action sequence first inverter seal output tube, and then the output terminals function inverter start to finish (52function) output is invalid, delay F15.46 time, power frequency switch effect (53function) F15.45=1 Manual switch Manual switching is when the specified phase angle difference is reached, the phase angle difference remains unchanged until the power frequency conversion (function 80 is active) is closed, the system to switch. Before running the Inverter Startup Is Completed terminal output is invalid (52 function), as running, at first the terminal function is valid, then delay F15.46 time, the inverter starts to output. 291 No.
Function Range Unit Default Type F15.44 Phase Angle Adjustment Enabled 0: Start Using 1: Shut Down 0 ● No. Function Range Unit Default Type F15.45 Frequency Converter -Power frequency Switch The Way 0: Automatic switch 1: Manual switch 0 〇 F15.46 The Switching Time 0~1000 ms 100 〇 No. Function Range Unit Default Type F15.47 Phase card startup latency 0~1000 ms 100 〇