EM500 Open-Loop Vector Control Inverter User Manual When the length count reaches 8(=2Ч4), “16: Length Reach” is enabled; when “39: Length Clear” is enabled, the count will be cleared and “16: Length Reach” output is disabled. EM500 inverter supports the count function (refer to Figure 7-42). The pulse information is inputted via the numeric input terminal. When the count reaches a set value, corresponding signal will be outputted. User may perform the programming with this signal (for example input it via DI/VX to be used as a stop command). User may view present count value via F18.33 in real time. F18.33 Designated Count Value Reach Signal Pulse Information DI 揅 ount?
Input (Function of No.34) Pulse Count n Cntin ≥ Designated Count Value Reach Signal Comparer 2 ≥ HDI 揜 apid Count? Input (Function of No.35) Clear Comparer 1 Designated Count Value n1 (1 - 65535) Set Count Value n2 (1 - 65535) Reset Count Clear Signal DI 揅 ounter Clear? Input (Function of No.36) ≤ ≤ 0 Figure 7-42 Block Diagram of Count Function Principle of work: When certain information is inputted in the form of pulse. DI terminal collects the information about the input pulse number n , and then compare it with the “Designated Count Value 1 n ”.
If 1 n n , it means that the “Set Count Value” has not been reached, otherwise it finishes and this result is output in the form of the terminal DO. Continue the count and compare it with the “Set Count Value.f 2 n n , it means that the “Set Count Value” has not been reached, otherwise it finishes and this result is outputted in the form of the terminal DO with the count stopping.“36: Counter Clear” is used to clear the counter and reset the output signal. If the pulse frequency is greater than 250 Hz (=1/(2(default filter times)*2*1ms -1 )), please complete 295 No.
Function Range Unit Default Type F16.03 Set Count Value F16.04 - 65535 1000 ● F16.04 Designated Count Value 1 - F16.03 1000 ● DO 揇esignated Count Value Reach? Output (Function of No.15) DO 揝et Count Value Reac Output (Function of No.14) h?