sinee — 7.17 F16 Group: User Defined Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual the input via X7 and set F02.06 as “35: High-Speed Count Input”: 250 Hz is just a theoretical value. The actual value will apply. To avoid any mistake, please use the high speed pulse input terminal. Pulse Input 2 1 3 4 5 6 7 8 9 10 11 Count 2 1 3 4 5 6 7 8 8 8 0 0 Clear Enabled Designated Output Disabled Disabled Disabled Enabled Disabled Set Output Figure 7-43 is an example. In the figure, F16.03=8 and F16.04=5. When the count Figure 7-43 Count (Example) reaches 5, “15: Designated Count Value Reach” is enabled; when the count reaches 8, “14: Set Count Value Reach” is enabled; when “36:

Counter Clear” is enabled, the count will be cleared and both “15: Designated Count Value Reach” and “14: Set Count Value Reach” are disabled. Set 65535≥Set Count Value≥Set-up Count Value≥0; if set count value = designated count value=0, then the counter is disabled; only one terminal can be set with this fu nction for the same time. This function code shall not be set as 0 to start the timed run function. When the running time reaches the set value, inverter stops and output terminal of the function “26: Set Time Reach” is enabled, with a prompt for the reach to the running time. by the input function “27:

Clear Timed Running time” (i.e., reset F18.35).When inverter User may view the remaining time through F18.35 or clear the preset running time is not running, this time indicates the set time; when inverter is running, this time refers 296 No. Function Range Unit Default Type F16.05 Set Timed Running time 0.0 - 6500.0, 0.0: Disabled min 0.0 ●