sinee — 7.18 F17 Group: Virtual I/O Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual In terms of functions, VY1 - VY8 are basically the same; they do not have an actual physical terminal, but they all have the positive/negative logic function. VY1 - VY4 have the delay function, with the same terminal status confirmation method; they can be set respectively. An example is given to VY1 in the following part. 302 Function F17.23 VY5Virtual Output Function 0 〇 F17.24 VY6 Virtual Output Function 0 〇 F17.25 VY7 Virtual Output Function 0 〇 F17.26 VY8 Virtual Output Function 0 〇 F17.27 Positive/Negative Logic of Virtual Input D7 D6 D5 D4 D3 D2 D1 D0 000 0000 0 〇 VY8 VY7 VY6 VY5 VY4 VY3 VY2 VY1 0:

Positive Logic, Enabled at On/Disabled at Off 1: Negative Logic, Disabled at On/Enabled at Off F17.29 VY1 Effective Delay Time 0.000 - 30.000 s 0.000 ● F17.30 VY1 Ineffective Delay Time 0.000 - 30.000 s 0.000 ● F17.31 VY2 Effective Delay Time 0.000 - 30.000 s 0.000 ● F17.32 VY2 Ineffective Delay Time 0.000 - 30.000 s 0.000 ● F17.33 VY3 Effective Delay Time 0.000 - 30.000 s 0.000 ● F17.34 VY3 Ineffective Delay Time 0.000 - 30.000 s 0.000 ● F17.35 VY4 Effective Delay Time 0.000 - 30.000 s 0.000 ● F17.36 VY4 Ineffective Delay Time 0.000 - 30.000 s 0.000 ● No.

Function Range Unit Default Type F17.28 Virtual Output Terminal Control D7 D6 D5 D4 D3 D2 D1 D0 111 11111 〇 VY8 VY7 VY6 VY5 VY4 VY3 VY2 VY1 0: To be determined by the status