EM500 Open-Loop Vector Control Inverter User Manual water supply basic groups; F26 group for clock water supply function of the advanced application group. The optional control mode is: Mode 1: A direct connection with the inverter's pump + sewage pump + auxiliary pump, In this mode, if the inverter is fault, the system will stop (the setting of inverter fault processing function is invalid). Mode 2: Two pumps connected to the inverter by contactor, one is the Primary pump and the other the standby pump.

In this mode, usually only the Primary pump works, if the motor overload occurs, output phase failure , the inverter will report "pump Error", but the system does not stop, the inverter will switch to standby pump to work, so that the water supply is not interrupted (requires the inverter fault handling function code to be set to "maintain the status quo"). a fault also occurs if the standby pump start, the inverter enters the Error state, system is shut down and reports the last error. Wiring diagram of water supply application : 311