EM500 Open-Loop Vector Control Inverter User Manual F25.04: Overpressure alarm pressure of pipe networks : When the feedback pressure exceeds the pipe network over-pressure alarm pressure, and continued until over-voltage protection action time is up, report E57 fault. F25.05: Under-voltage alarm pressure of pipe networks : When the feedback pressure is lower than the undervoltage alarm pressure, and until continued over-voltage protection action time is up, report E58 fault. F25.16=0: No H Pump It means that H pump has no function . F25.16=1: H Pump is Sewage pump The terminal set to H pump is processed according to the treatment logic of the sewage pump.

The sewage pump is effective when setting the upper and lower water level input terminals of the sewage tank. F25.16=2: H Pump is primary pump(OnlyF25.00=0) The terminal set to H pump must be used in conjunction with I pump set to auxiliary 314 No. Function Range Unit Default Type F25.04 Overpressure alarm pressure of pipe networks 0.1~F09.03 %/ MPa 100.0 ● F25.05 Under-voltage alarm pressure of pipe networks 0.1~F09.03 %/ MPa 0.1 ● F25.06 Overpressure and under-voltage protection action time 0~3600 s/M Pa 500 ● No. Function Range Unit Default Type F25.16 H Pump Definition 0: No H Pump 1: H Pump is Sewage pump 2: H Pump is primary pump(OnlyF25.00=0) 0 〇 F25.17 I Pump Definition 0:

No I Pump 1: I Pump is Auxiliary(Sleep) pump 2:I Pump is Emergency pump (Only F25.00=0) 0 〇