sinee — 7.21 F25 Application of water supply basic groups

EM500 Open-Loop Vector Control Inverter User Manual pump, and set the pump's rotation function to be effective. F25.17=0: No I Pump It means that I pump has no function . F25.17=1: I Pump is Auxiliary(Sleep) pump The terminal set to I pump will perform the action according to the parameter setting. If the PID reaches the sleep condition, the auxiliary pump will operate when the sleep is valid and not the offline sleep. F25.17=2: 2:I Pump is Emergency pump (Only F25.00=0) The terminal set to I pump needs to be used in conjunction with the H pump set as the Primary pump, and the rotation function of the pump after setting is effective. 1.

The upper limit level and lower limit level is not set for Inlet pool, it will report E56 fault in running time 。 2. When the sewage pump detection function is valid, if the H pump is set as sewage pump, E56 will be reported when running. 3. When sewage pool function is effective , if the upper limit water level of the sewage pool and the lower limit water level of the sewage pool are not set at the same time, E56 failure will be reported when running. 4.H Pump refers to the output terminal whose code is set to 63 and I pump corresponds to code 64. The function code applies to the Primary pump and standby pump switch, to solve the electromagnetic switch action delay caused by the problem.

F25.29 = 0, the pump timing switch function and the pump terminal switch function are invalid. 315 No. Function Range Unit Default Type F25.19 Electromagnetic switch switching time 0.1~5.0 S 0.5 〇 No. Function Range Unit Default Type F25.29 Pump Timing Rotation cycle 0~9999 h 0 ● No. Function Range Unit Default Type F25.30 Rapid pump 0: The normal rotation clock 0 ●