EM500 Open-Loop Vector Control Inverter User Manual PID control parameters are adjusted as per actual applications. F28.35 / F28.36 are to control the upper limit and lower limit of temperature PID output respectively. When the feedback temperature is higher than the set temperature of F28.28 upon the se time of F28.39, the fan will start operation, namely fan start, output terminal function code is valid. When the feedback temperature is lower than the set temperature of F28.37 upon the set time of F28.38, the fan will stop, the output terminal function code 50 is valid. When the absolute value of error is less than this range, the PID function stops.
When the feedback reaches at the set value for the first time, the limit deviation starts to act, PID function stops, when it is beyond the range, the limit deviation fails and PID restarts. Disconnection detection value, when the feedback pressure is less than the set value of this function code, the program will start counting, and till the set time of F28-42 is up, 345 Limit Temperature F28.36 regulation 0.00~100.00 % 100.00 ● Lower Limit No. Function Range Unit Default Type Fan stop 0.00~ Maximum temperature F28.37 ℃ 70.0 ● temperature range Stopping F28.38 temperature 10~7200 s 1200 ● running time Fan start delay F28.39 1~300 s 10 ● time No.
Function Range Unit Default Type Temperature limit F28.40 0.00~100.00 % 0.00 ● deviation No. Function Range Unit Default Type Temperature F28.41 disconnection 0.0~ Maximum temperature range ℃ 8.0 〇 detection threshold Temperature 0.0~6000.0, 0.0 :The Function is F28.42 disconnection s 0.0 ● Disabled detection Time