EM500 Open-Loop Vector Control Inverter User Manual the system will report E48 fault 。 When F28.25 ten place is 0, the motor temperature can be detected through the analog input channel. The maximum value of the analog input is 200 degrees. The offset of the analog input can be changed when the maximum range of the sensor does not match the value. When the detected temperature is higher than the value set in F 28.44, the inverter will report E49 fault. After the fault, the temperature needs to be less than F28.44 set temperature -25 degree to run normally again.
When the inverter display temperature is less than the value of F28.45 and maintain F28.64 set time, the inverter reported E50 failure 346 No. Function Range Unit Default Type 0: AI1 Motor 1: AI2 F28.43 Temperature 2: AI3 2 〇 feedback selection 3: AI4 4: HDI No. Function Range Unit Default Type Motor overheating F28.44 25.0~200.0 ℃ 110.0 〇 threshold No. Function Range Unit Default Type Motor PTC F28.45 disconnection 0.0~50.0 ℃ 8.0 〇 detection threshold Motor PTC 0.00~6000.0, 0.0:The Function is F28.46 disconnection s 0.0 ● Disabled detection Time No.
Function Range Unit Default Type Oil filter using F28.47 0~9000 h 4500 ● time preset oil separator using F28.48 0~9000 h 4500 ● time preset Air filter using F28.49 0~9000 h 4500 ● time preset Lubricating oil F28.50 0~9000 h 4500 ● using time preset F28.51 Grease using time 0~9000 h 4500 ●