sinee — 7.24 F28 Air Compressor Application

EM500 Open-Loop Vector Control Inverter User Manual Used to set the corresponding time, the inverter will record the actual operation time, when the use of time is beyond the alarm delay time, E51 failure occurs. F28.53=0: Not Used Indicates no operation F28.53=1: Reset After setting the code, the running time and the current power is cleared, after that, it is cleared automatically.

This function code setting time is when the inverter meets the unloading condition, manually loading, the loading valve will open and then automatically shut down when the set time of F28.54 is up, if the pressure is greater than the warning pressure before the set time is up, the valve will shut down in advance. 347 preset Preset alarm delay F28.52 0~100 h 10 ● time No. Function Range Unit Default Type The Power meter 0: No Used F28.53 0 ● timing reset 1: Reset No. Function Range Unit Default Type Inching loading F28.54 0~60 s 3 〇 delay No. Function Range Unit Default Type First place: mechanical maintenance time is up Second place: Pressure overrun protection Third place:

Pressure feedback wire cut protection Fourth place: Temperature overrun protection 0000 F28.55 Protection block 〇 Fifth place: Temperature feedback 0001 wire cut protection Sixth place: Not Used Seventh place: The motor feedback wire cut protection Eighth place: Not Used From right to left (0- No shield 1-shield )