EM500 Open-Loop Vector Control Inverter User Manual After setting, can be used to block the corresponding fault F28.66 and F28.67 are used to set the function of the JZ / BJ terminal on the interface card (ie the two terminals can be used for other purposes) F28.68=0: JT Normally closed At this point the air compressor interface card JT terminal logic is as follows: JT1 and JT2 short cut then emergency stop is invalid, disconnect and the emergency stop is valid, and the inverter will coast to stop F28.68=1: JT Normally open At this point the air compressor interface card JT terminal logic is as follows:
JT1 and JT2 short cut and emergency stop is valid, and the inverter will coast to stop, disconnect and the emergency stop is invalid. 348 No. Function Range Unit Default Type JZ Multi-function See the output terminals function F28.66 49 〇 set table BJ Multi-function See the output terminals function F28.67 7 〇 set table No. Function Range Unit Default Type Interface card Positive and 0: JT Normally closed F28.68 0 〇 negative logic 1: JT Normally open setting No. Function Range Unit Default Type Ones Place: Interface board oil temperature 0: Curve 1 1: Curve 2 2: Curve 3 3: Curve 4 Sensor offset curve Tens Place: Interface board Motor F28.69 120 〇 setting temperature 0: Curve 1 1: Curve 2 2:
Curve 3 3: Curve 4 hundreds place: Interface board pressure