EM500 Open-Loop Vector Control Inverter User Manual Rotational autotuning is applied to the occasions when motor can be disconnected from load. Before autotuning, motor should be disconnected from Make sure that motor is in stop status before autotuning; otherwise, autotuning can load. Never perform rotational autotuning for a motor with load. not be performed normally. Autotuning is only enabled when inverter is in keypad control mode (F00.02=0). To ensure normal autotuning, set all motor parameters as per the values listed on motor nameplate correctly: F01.00: Motor model, F01.01: Motor rated power, F01.02: Motor rated voltage, F01.03: Motor rated current, F01.04:
Motor rated frequency, F01.05: Motor rated speed, F01.06: Motor wiring method and F01.07: Motor rated power factor. Based on the rated power of inverter, match inverter with To ensure the control performance, motor and inverter should match in terms of the an applicable Y-series motor, and the defaults of motor can meet most of needs. power rating. Usually, power rating of motor is only allowed to be one level lower than that of inverter. After autotuning finishes normally, the setting value of F01.09 - F01.13, F01.19 – When F12.14=1 reset the default, the parameters of F01.00 - F01.13, F01.19 – F01.22 will be updated and auto-saved. F01.22 remain unchanged.
8.3 Steps of Autotuning In parameter setting status, set F00.2=0, and disconnect motor from load. Set all motor parameters as per the values listed on the nameplate correctly: F01.00: Motor model, F01.01: Motor rated power, F01.02: Motor rated voltage, F01.03: Motor rated current, F01.04: Motor rated frequency, F01.05: Motor rated speed, F01.06: Motor wiring method and F01.07: Motor rated power factor. For asynchronous induction motor By setting F01.34=1, and pressing RUN , inverter starts stationary autotuning for motor. Or by setting F01.34=2, and pressing RUN , inverter starts rotational 353