sinee — 9.1 Faults

EM500 Open-Loop Vector Control Inverter User Manual 9. Troubleshooting 9.1 Faults When something abnormal happens to inverter, keypad will display corresponding fault code and parameter; the fault relay is on, the fault output terminal is on, inverter output stops. If motor is still running when a fault occurs, it will stop by the setting mode. For EM500 faults and countermeasures, see Table 9-1. Table 9-1 EM500 Faults and Troubleshooting 355 Fault Code Fault type Cause Troubleshooting SC Short Circuit/EMC Fault 1. Short circuit between output phase and ground 2. Short circuit between phases 3. Short circuit of external brake resistor 4. Acceleration/deceleration time is too short 5.

Power module is damaged 6. Field interference 1. Check if there is any short circuit phenomenon. 2. Extend acceleration/ deceleration time 3. Investigate causes and reset after taking appropriate measures. 4. Seek for technical support. HOC Instantaneous Overcurrent 1. Short circuit between inverter output phases 2. Acceleration/deceleration time is too short. 3. Under V/F control mode, V/F curve has been set irrationally. 4. Motor is running when inverter starts. 5. Motor exceeds inverter capacity or load is too heavy. 6. IGBT damaged (HOC). 1. Check if there is any short circuit phenomenon in wiring. 2. Extend acceleration/ deceleration time. 3. Set VF curve rationally. 4.

Enable the revolution track or start DC brake. 5. Replace with an appropriate motor or inverter. SOC Stable Overcurrent HOU Instantaneous Overvoltage 1. Deceleration time is too short and regenerated energy is too large. 2. Input voltage is too high. 1. Extend deceleration time. 2. Select an appropriate braking unit/braking resistor.