EM500 Open-Loop Vector Control Inverter User Manual 356 3. Lower the input voltage to the specified range. SOU Stable Overvoltage 1. Power grid voltage is too high. 2. Deceleration time is too short. 1. Lower the voltage to the specified range. 2. Extend deceleration time SlU Stable Undervoltage 1. Input voltage phase loss. 2. Wiring terminals of input voltage are loosened. 3. Input voltage drops too much. 4. Aging of switch contact on input power supply. 1. Check the input voltage and its wiring. 2. Tighten screws of input wiring terminal. 3. Check air switch and contactor. IlP Input Phase Loss 1. Input voltage phase loss (rated power). 1. Check input voltage. 2. Check input voltage wiring.
3. Check whether the connection terminals are loosened. OlP Output Phase Loss 1. Phase loss of U, V or W 1. Check the connection between inverter and motor. 2. Check whether motor winding is disconnected; 3. Check whether output terminals are loosened. Ol Inverter Overload 1. Acceleration/deceleration time is too short. 2. Under V/F control mode, V/F curve has been set irrationally. 3. Load is too heavy. 4. Braking time is too long; Repeated dc brake 1. Extend acceleration/deceleration time. 2. Set VF curve rationally. 3. Replace inverter with another one that matches with the load. 4. Reduce braking time; Do not repeatedly dc brake OH Radiator overheating 1. Ambient temperature is too high.
2. Inverter is in poor ventilation. 3. Cooling fan fault. 1. Running conditions of inverter shall comply with specification requirements. 2. Improve ventilation environment and check whether air duct is blocked. 3. Replace the cooling fan.