EM500 Open-Loop Vector Control Inverter User Manual 357 E11 Parameter Setting Conflict 1. Parameter setting logic conflict 1. Check whether parameters set prior to a fault is unreasonable. E12 Motor Overload 1. Detection of motor temperature is greater than the threshold 2. Motor temperature sensor is broken. 3. Ambient temperature is too high 4. The load is too heavy 1. Check motor temperature threshold. 2. Check motor temperature sensor 3. Improve heat dissipation of the motor 4. Choose the proper motor E13 Motor Overload 1. Acceleration/deceleration time is too short. 2. Under V/F control mode, V/F curve has been set irrationally. 3. Load is too heavy. 1.
Extend acceleration/deceleration time. 2. Set VF curve rationally. 3. Replace inverter with another one that matches with the load. E14 External Fault 1. Peripheral fault terminal acts. 1. Check peripherals. E15 Inverter EEPROM Fault 1. Interference results in reading and writing errors of EEPROM. 2. EEPROM damaged. 1. Press STOP/RESET to reset and then try it again. 2. Seek for technical support. E16 Communication Abnormality 1. the communication timeout is enabled for discontinuous communication system 2. SCI communication failure 1. Set F10.03 to 0.0 for discontinuous communication system 2. Check whether the communication cable is disconnected. 3.
Adjust the communication overtime (F10.03). E17 Invertor Temperature Sensor Abnormality 1. Temperature sensor of inverter is off or short-circuited. 1. Check whether temperature sensor of inverter is properly wired. 2. Seek for technical support E18 Soft Start Relay Off 1. The grid is interrupted 2. Input voltage phase loss. 3. Wiring terminals of input voltage are loosened. 1. interruption of power supply should be done after the inverter stopped