EM500 Open-Loop Vector Control Inverter User Manual 358 4. Input voltage drops too much. 5. Aging of switch contact on input power supply. 2. Check the input voltage and its wiring. 3. Tighten screws of input wiring terminal. 4. Check air switch and contactor. E19 Current Detection Circuit Abnormality 1. Detection circuit of drive board or control board is damaged. 1. Seek for technical support. E20 Stall Fault 1. The set deceleration time is excessively short; 2. Energy consumption brake abnormality at ramp-to-stop. 1. Increase the set deceleration time. 2. Check energy consumption brake status. E21 PID Feedback Disconnection 1.
PID feedback is higher than upper limit F09.24 or lower than lower limit F09.25, depending upon types of sensors . 1. Check whether the feedback line falls off; 2. Check whether the sensor works abnormally; 3. Adjust the feedback disconnection detection value to a reasonable level. E22 Not Used E23 Keypad EEPROM Fault 1. Interference results in reading and writing errors of the EEPROM. 2. EEPROM damaged. 1. Press STOP/RESET to reset and then try it again. 2. Seek for technical support. E24 Autotuning Abnormality 1. Press STOP/RESET in the parameter autotuning. 2. In autotuning, the external coast-to-stop terminal FRS=ON. 3. Motor is not connected to output terminal of inverter. 4.
Motor is not disconnected from load for rotational autotuning. 5. Motor fault. 1. Press STOP/RESET to reset. 2. Check the connection between inverter and motor. 3. Motor is disconnected from load for rotational autotuning. 4. Check motor. E25 Not Used E26 Offload 1. Enabled when motor 1. The load is excessively light