sinee — 9.1 Faults

EM500 Open-Loop Vector Control Inverter User Manual 359 Protection current is lower than offload detection level F07.22 and this status is maintained for the time set through F07.23 2. Current detection module is damaged or the offload level is not reasonable; 2. Offload; 3. Current detection module is damaged 4. Seek for technical support E27 Accumulated Power-On Time is up It is time for maintenance 1. Contact dealer. E28 Accumulated Running time is up It is time for maintenance 1. Contact dealer. E29 Internal Communication Fault 1. Internal SPI communication fault 1. Power-on after power cut. 2. Seek for technical support. E30 - E32 Not used E33 CANopen Communication Overtime 1.

Data Communication Overtime 1. Ensure that inverter is powered on again after the line is smooth. E34 DeviceNet without Network Power Supply 1. No DC24V Power Supply is detected for DeviceNET bus 1. Power supply backs to normal E35 DeviceNet BUS-OFF 1. Short circuit between CAN H and CAN L of _ _ DeviceNet bus 1. Ensure that wiring is normally E36 DeviceNet MACID Detection Error 1. There is already the same station on the bus 1. Power on inverter after address modification E37 DeviceNet IO Communication Overtime 1. NO IO message received within specified time during online status 1. Ensure that inverter is powered on again after the line is smooth. E38 DeviceNet IO Mapping Error 1.

Non-existence of IO Polling Data Address 1. Make sure to input a correct parameter address E39 Profibus-DP 1. Incompliance of 1. Make sure to receive correct