EM500 Open-Loop Vector Control Inverter User Manual 360 Parameterizatio n Data Error parameterization data sent by master with specification parameterization data E40 Profibus-DP Configuration Data Error 1. The configuration data sent by master is not supported by slave card 1. Make sure to receive correct configuration data E41 Profibus-DP IO Disconnection 1. At normal data exchange status, DP card has not received any data for a long time (disconnection between DP card and master), so it exists data exchange status. 1. Enter data exchange status restoration fault E42 Not Used E43 Material supply disruptions Error 1.
When the external signal is detected, the external signal terminal is closed. 2. In automatic detection, the feedback is greater than the voltage limit or feedback is less than the voltage lower limit. 1. Reduce starting feed forward and soft start feedforward gain when starting disconnection. 2. The shock disconnection in operation, Increase or decrease the ratio P. 3. Check whether the sensor is loose lead. E44 Winding traverse Error 1.The cable detection terminal valid time is too long. 2. Cable detection terminal invalid time is too long. 1.Check if the sensor is working properly. 2.Check whether the terminal can be judged normally closed.
E45 Air pressure over voltage Error 1.The sensor feedback pressure is too high. 2.The analog input terminals are damaged 1. Check the sensor for abnormalities. 2. Check whether the analog terminals can detect the analog input normally. 3. Check the external devices. E46 Air pressure feedback 1. The sensor feedback pressure is too low. 1. Check the sensor for abnormalities.