EM500 Open-Loop Vector Control Inverter User Manual 362 3. Check the external devices. E51 It's Time For Mechanical Maintenance 1. F28.81 ~ F28.85 record time is greater than F28.47 ~ F28.51 plus F28.52 time, that means the maintenance time is up. 1. Timely maintenance of mechanical equipment and then manually F28.81 ~ F28.85 for zero treatment. E52 Not Used E56 Pump Error 1. occurs only when the water supply is in standby mode, plus the Primary pump mode, which drives a pump motor overload output phase fault. 1. Check if the load is too heavy. 2. Check if the output line is loose E57 Pipe networks Overpressure 1. Feedback pressure in water supply applications is too high. 1.
Check the sensor for abnormalities. 2. Check whether the analog terminals can detect the analog input normally. 3. Check the external devices. E58 Pipe networks Undervoltage 1.The feedback pressure in water supply applications is small. 1. Check the sensor for abnormalities. 2. Check whether the analog terminals can detect the analog input normally. 3. Check the external devices. E59 water supply tank Water shortage 1. The sensor is abnormal. 1. Check the sensor for abnormalities. E60 Not Used E61 CANSinee Communication Timeout 1.Data communication timeout 1.Make sure that the line is unblocked and power on again.