sinee — 13.2.2 Baud rate and transmission distance

EM500 Open-Loop Vector Control Inverter User Manual 13. CANSinee Communication Protocol 13.1 Application Scope 1. Applicable series: EM500 2.Applicable network: Inverter with CAN bus interface - Inverter master-slave communication, and communication between client and inverter 13.2 Physical Interfaces 13.2.1 Bus topology CAN bus connection topology as shown below, CAN bus recommended shielded twisted pair connection, the bus ends are connected to two 120Ω termination resistor to prevent signal reflection. Shield generally use a single point of reliable grounding.

Figure 13- 1 CAN bus topology diagram 13.2.2 Baud rate and transmission distance The maximum length of the CAN bus depends on the communication speed, Specific provisions are as follows: 411