EM500 Open-Loop Vector Control Inverter User Manual get a normal response. A query by the master may result in one of the following four times: If the slave device receives a request with no communication error and can process the query normally, the slave device will return a normal response. If the slave device receives a request for no communication error but can not process the request (such as requesting a non-existent register), the slave will return an exception response informing the master of the actual error. Exception response message has two different domains to normal response : Function code field:
In the normal response, the slave replicates the function code of the original request in the corresponding function code field. The LSB of the 4-bit function code is 0. In the exception response, the slave sets the LSB of the function code to 1. Namely, the abnormal response function code = normal response function code +1 Data field: In the normal response, the slave can return the exception code 00H in the data field. In the abnormal response, the slave returns other exception codes in the data field.
The specific exception codes are shown in Table 3- 1 Table 3-1 Definition of abnormal codes 421 Abnormal Name Implication code 00H normal The received data from the slave (inverter) can be parsed normally 01H Illegal function The function code received by the slave (drive) has exceeded the configured range 02H Illegal data address The data address received by the slave (inverter) is not an allowed address; in particular, the combination of the start address and the transfer length of the register is invalid 03H Illegal data frame The length of the data received by the slave (inverter) is not correct