sinee — 6.2 Function Parameter Table

EM600 High-Performance Vector Control Inverter User Manual 105 Function Name of Function Parameter Description Unit Default Property Code Code 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) F15.08 Deceleration Time 4 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.09 Acceleration/Deceler ation Time Reference Frequency 0: Maximum Frequency F00.16 1: 50.00 Hz 0 〇 F15.10 Automatic Switching between Acceleration and Deceleration Time 0: Disabled 1:

Enabled 0 〇 F15.11 Switching Frequency between Acceleration Time 1 and Acceleration Time 2 0.00 Hz - Maximum Frequency F00.16 Hz 0.00 ● F15.12 Switching Frequency between Deceleration Time 1 and Deceleration Time 2 0.00 Hz - Maximum Frequency F00.16 Hz 0.00 ● F15.13 Acceleration/Deceler ation Time Unit 0:0.01s 1:0.1s 2:1s 0 〇 F15.14 Hopping Frequency Point 1 0.00 - 600.00 Hz 600.00 ● F15.15 Frequency Hopping Range 1 0.00 - 20.00 Disabled at 0.00 Hz 0.00 ● F15.16 Hopping Frequency Point 2 0.00 - 600.00 Hz 600.00 ● F15.17 Frequency Hopping Range 2 0.00 - 20.00 Disabled at 0.00 Hz 0.00 ● F15.18 Hopping Frequency Point 3 0.00 - 600.00 Hz 600.00 ● F15.19 Frequency Hopping Range 3 0.00 - 20.00 Disabled at 0.00 Hz 0.00 ● F15.20 FAR Detection Bandwidth 0.00 - 50.00 Hz 2.50 〇 F15.21 Output Frequency Detection Range FDT1 0.00 - Maximum Frequency F00.16 Hz 30.00 〇 F15.22 FDT1 Hysteresis -(Fmax-F15.21)~F15.21 Hz 2.00 〇 F15.23 Output Frequency Detection Range 0.00 - Maximum Frequency F00.16 Hz 20.00 〇