sinee — 7.1 F00 Group: General Parameter

EM600 High-Performance Vector Control Inverter User Manual F00.05=0: Numeric frequency setting F00.07 Auxiliary frequency B is determined through numeric frequency setting F00.07. F00.05=1: AI1 F00.05=2: AI2 F00.05=3: AI3 F00.05=4: AI4 (Expansion Card) Auxiliary frequency B is determined through AI (percentage) * F00.16 (or F14.78). F00.05=5: High-Frequency Pulse Input (X7) Auxiliary frequency B is determined through HDI (percentage) * F00.16 (or F14.78). 123 Terminal Function Description Priority Frequency Setting F00.04=0. 52:

Switch Main Frequency Source to AI1 If enabled, main frequency source A is determined by the percentage inputted through AI1, for which refer to description of F00.04=1. 3 53: Switch Main Frequency Source to AI2 If enabled, main frequency source A is determined by the percentage inputted through AI2, for which refer to description of F00.04=2. 4 54: Switch Main Frequency Source to AI3 If enabled, main frequency source A is determined by the percentage inputted through AI3, for which refer to description of F00.04=3. 5 55:

Switch Main Frequency Source to High-Frequency Pulse Input If enabled, main frequency source A is determined by the percentage inputted through high-frequency pulse input, for which refer to description of F00.04=5. 6 56: Switch Main Frequency Source to Communication Setting If enabled, main frequency source A is determined through communication, for which refer to description of F00.04=6. 7 -- If neither of terminals above is enabled, main frequency source A is determined through F00.04. 8 Function Name of Function Parameter Description Unit Default Property Code Code F00.05 Auxiliary Frequency Source B 0: Numeric frequency setting F00.07 1: AI1 2: AI2 3: AI3 4: AI4 (Expansion Card) 5:

High-Frequency Pulse Input (X7) 6. Auxiliary Frequency Communication Percentage Setting 7. Auxiliary Frequency Communication Direct Setting 8 - 9: Not Used 10: Process PID 11: Simple PLC 0 〇