sinee — 7.1 F00 Group: General Parameter

EM600 High-Performance Vector Control Inverter User Manual Please refer to the description of F00.04 for detailed explanations of AI1-AI4 and X7. F00.04 has the same meanings as AI1-AI4 and X7. 100.00% is the percentage inputted through F00.16 (or F14.78) (Maximum Frequency). F00.05=6 or 7: Main Frequency Communication Setting Auxiliary frequency B is determined through communication control, etc.  If inverter is under master-slave communication control (F10.05=1) and present inverter is a slave (F10.06=0), auxiliary frequency B is set as “700 FH (Master-Slave Communication Setting) * F00.16 (or F14.78) (Maximum Frequency) * F10.08 (Receiving Proportionality Factor of Slave)”.

Range of 700 FH is -100.00% to 100.00%. See Table 12-2 for details.  For general communication (F10.05=0): a) F00.05=6 Auxiliary Frequency Communication Percentage Setting. Auxiliary frequency source A is set as “7002H (communication setting of auxiliary channel frequency B) * F00.16 (or F14.78) (Maximum Frequency)”. b) F00.05=7 Auxiliary Frequency Communication Direct Setting. Auxiliary frequency source B is set as “7016H (communication setting of auxiliary channel frequency B)”. The range of 7002H is -100.00% to 100.00%. The range of 7016H is 0.00 to F00.16 (Maximum Frequency). See Table 12-2 for details. F00.05=10:

Process PID Auxiliary frequency B is determined by output of Process PID (refer to 7.10). Generally, it is used for on-site closed loop control mode, for example closed loop control under constant pressure and closed loop control under constant tensile force. F00.05=11: Simple PLC Auxiliary frequency B is determined by output of Simple PID (refer to 7.9). Select final frequency setting channel and arithmetic mode. F00.06=0 : Main Frequency Source A Final setting frequency is only determined through main frequency source A. 124 1. Main frequency source A and auxiliary frequency source B can not select the same physical channel (AI1-4/X7); 2.

Process PID or simple PLC will be enabled only after being selected. Function Name of Parameter Description Unit Default Property Code Function Code F00.06 Frequency Source Options 0: Main Frequency Source A 1: Auxiliary Frequency Source B 2: Main and Auxiliary Arithmetic Results 3: Switching between Main Frequency Source A and Auxiliary Frequency B 4: Switching between Main Frequency Source A and Main & Auxiliary Arithmetic Results 5: Switching between Auxiliary Frequency Source B and Main & Auxiliary Arithmetic Results 0 〇