sinee — 7.1 F00 Group: General Parameter

EM600 High-Performance Vector Control Inverter User Manual frequency coming down from acceleration/deceleration reference frequency Fbase to 0.00Hz; this has nothing to do with forward/reverse. See Figure 7-4. Output Frequency (Hz) Fbase Output Frequency (Hz) Fbase Fbase Fbase t1 t (s) t2 t (s) (a)Acceleration Time 1 (b)Deceleration Time 1 Figure 7–4 Acceleration/Deceleration Time F00.16 is the maximum frequency allowed by inverter and denoted by Fmax (range: 1.00 - 600.00 Hz). F00.17=0: Set through F00.18 Under torque control mode, upper limit frequency is set through F00.18. F00.17=1: AI1 F00.17=2: AI2 F00.17=3: AI3 F00.17=4: AI4 (Expansion Card) 128 Note:

there are three acceleration/deceleration time units, 0.01 s, 0.1 s and 1 s, which are determined through F15.13. Name of Function Code Parameter Description Unit Default Property Function Code F00.16 Maximum frequency 1.00 - 600.00 Hz 50.00 〇 Function Name of Function Parameter Description Unit Default Property Code Code F00.17 Upper Limit Frequency Control Options 0: Set through F00.18 1: AI1 2: AI2 3: AI3 4: AI4 (Expansion Card) 5: High-Frequency Pulse Input (X7) 6: Communication Percentage Setting 7:

Communication Direct Setting 0 〇 F00.18 Upper Limit Frequency Lower Limit Frequency F00.19 - Maximum Frequency F00.16 Hz 50.00 ● F00.19 Lower Limit Frequency 0.00 - Upper Limit Frequency F00.18 Hz 0.00 ●