EM600 High-Performance Vector Control Inverter User Manual Under torque control mode, upper limit frequency is set through AI (percentage) * F00.18. F00.17=5: High-Frequency Pulse Input (X7) Under torque control mode, upper limit frequency is set through HDI (percentage) * F00.18. Please refer to the description of F00.04 for detailed explanations of AI1-AI4 and X7. F00.04 has the same meanings as AI1-AI4 and X7. 100.00% is the percentage inputted through F00.18 (Upper Limit Frequency). F00.17=6 or 7: Communication Setting Torque is determined by communication, etc.
For master-slave communication (F10.05=1) and the inverter is slave (F10.06=0) upper limit frequency is set as “700FH (Main Frequency Setting by Communication) * F00.18 (upper limit frequency)* F10.08 (Receiving Proportionality Factor of Slave)”. The range of 700FH is -100.00% to 100.00%. See Table 12-2 for details. For general communication (F10.05=0) a) For F00.17=6, upper limit frequency is “ 700AH (communication setting of upper limit frequency) * F00.18 (upper limit frequency) ” .
b) For F00.17=7, upper limit frequency is “ 7017H (communication setting of upper limit frequency) ” , set percentage is “700AH (Communication Setting of Upper Limit Frequency) * F00.18 (Upper Limit Frequency)”. Range of 700AH is 0.00% to 200.00%. See Table 12-2 for details. F00.18 is the maximum operating frequency after inverter starts and denoted by Fup (range: Fdown - Fmax). F00.19 is the minimum operating frequency after inverter starts and denoted by Fdown (range: 0.00 Hz - Fup). By changing the function code, user may reverse motor rotation direction without changing motor wiring.
Its function is the same as the switching of any two terminals of motor (U, V and W) in turning motor rotation direction. 129 1. Upper limit frequency and lower limit frequency shall be set carefully according to nameplate parameters and applications of the controlled motor. Otherwise, motor, after having worked for a long time at a low frequency, would lose its service life due to overheating. 2. The relationship among maximum frequency, upper limit frequency and lower limit frequency is: 0.00 Hz≤Fdown≤Fup≤Fmax≤600.00 Hz. 3. When set frequency is lower than F00.19 (lower limit frequency), running mode of inverter is determined through F15.33.
Name of Function Code Parameter Description Unit Default Property Function Code F00.20 Running Direction 0: Same 1: Opposite 0 ● 1. After parameter initiliazation, running direction of motor will be restored to original status. 2. After system debugging, this function shall be used with caution for the