EM600 High-Performance Vector Control Inverter User Manual F00.21=0: Enabled Rotation direction of motor can be controlled by set F/R terminal or F00.20. F00.21=1: Disabled If motor can run at one direction only, then neither terminal F/R nor F00.20 is enabled. Select the status when motor switches between forward and reverse. If F00.22=0.00, switch between forward and reverse completes smoothly. If F00.22≠0, then inverter runs for the time as set through F00.22 at 0.00 Hz and runs at the reverse direction until set frequency is reached, after rotation speed decreases to 0.00 Hz at the time of switching between forward and reverse. See Figure 7–5.
Output frequency Time F/R Deadband Time F/R Deadband Time Figure 7–5 Forward/Reverse Deadband Time 130 occasion where motor is not allowed to be reversed. 3. This function is disabled, if inverter is not allowed to be reversed (for example F00.21=1). Name of Function Function Code Parameter Description Unit Default Property Code F00.21 Reverse Control 0: permit forward/reverse 1: prohibit reverse 0 〇 F00.22 F/R Deadband Time 0.00 - 650.00 s 0.00 ● If reverse is permitted, inverter judges direction according to status of terminal F/R and the value set through F00.20.
If set forward direction is inconsistent with the wished motor direction, switch any two of inverter’s output terminals U, V and W, or change F00.20 to an inverse value. Function Name of Parameter Description Unit Default Property Code Function Code F00.23 Carrier Frequency 1.0 - 16.0 (inverter rated power kHz 8.0- 2.0 ●