sinee — 7.1 F00 Group: General Parameter

EM600 High-Performance Vector Control Inverter User Manual When carrier frequency is higher than the default value, increasing carrier frequency by 1 kHz requires load to decrease to some extent. Please set F00.24=1, and at this time, inverter will automatically adjust actual carrier frequency based upon actual application. It's recommend to set the the relationship between inverter’s rated power and carrier frequency as shown in Table 7–2. Table 7-2 Setting Relationship between Inverter Rated Power and Carrier Frequency F00.24=0: Disabled Carrier frequency is set through F00.23, limited by maximum carrier and will not change during running. F00.24=1:

Enabled Carrier frequency set through F00.23 is affected by inverter temperature and load level. If inverter has an excessively high temperature or load, carrier wave will be limited. When set carrier frequency F00.23 is greater than limit value, limit value shall be used as carrier frequency of inverter. When noise suppression function is enabled (F00.25=1), a sine wave may be superposed on the basis of set carrier wave (the frequency is set through F00.26 and intensity is set through F00.27), which may suppress present motor noise to some extent. EM600 inverter supports time interval based control of two motors, of which motor parameter and control parameter can be set separately.

Motor 1 corresponds to parameters of F00, F01 and F06, and motor 2 corresponds to parameters of F14. 131 Inverter Frequency Pe Pe≤4kW 5.5kW - 7.5kW 11kW - 45kW 55kW - 90kW 110kW - 560kW Rated Carrier 8.0 kHz 6.0kHz 4.0kHz 2.0kHz 2.0kHz Maximum Allowed Carrier 16.0 kHz 10.0kHz 8.0kHz 4.0kHz 3.0kHz Name of Function Code Parameter Description Unit Default Property Function Code F00.24 Automatic Adjustment of Carrier Frequency 0: Disabled 1: Enabled 1 〇 Function Name of Function Parameter Description Unit Default Property Code Code F00.25 Carrier Frequency Noise Suppression 0: Disabled 1:

Enabled 0 〇 F00.26 Noise Suppression Tone 20 - 200 Hz 40 ● F00.27 Noise Suppression Intensity 10 - 150 Hz 100 ● Name of Function Function Code Parameter Description Unit Default Property Code F00.28 Motor Parameter Group 0: Motor 1 Parameter 1: Motor 2 Parameter 0 〇