sinee — 7.3 F02 Group: Input Terminal Parameter

EM600 High-Performance Vector Control Inverter User Manual Xi Input On Off Positive Logic Sampling Enabled Disabled Enabled Disabled Reverse Logic Sampling Figure 7-7 Terminal Positive and Negative Logic Sampling 144 Set Function Description Value 57 Inverter Enabled If inverter meets other running applications and this terminal is enabled, then inverter can run; otherwise, inverter can not run if the inver meets other running conditoins but this terminal is disabled. ★ Enable inverter:

if no terminal option is selected, the default is enabled; if there is only one terminal option, the selected terminal status works; if there are more than one terminal, this terminal will be disabled as long as one of the selected terminals is disabled. 58 - 68 Not Used 69 Reverse Forbidden When this Terminal is enabled, function is tha same as F00.21=1 70 - 124 Not Used Function Name of Parameter Description Unit Default Property Code Function Code F02.15 Positive/Nega tive Logic 1 of Numeric Input Terminal D7 D6 D5 D4 D3 D2 D1 D0 *00 00000 〇 * X7 X6 X5 X4 X3 X2 X1 0: Positive Logic, Enabled at On/Disabled at Off 1:

Negative Logic, Disabled at On/Enabled at Off F02.16 Positive/Nega tive Logic 2 of Numeric Input Terminal D7 D6 D5 D4 D3 D2 D1 D0 000 00000 〇 X11 X10 X9 X8 AI4 AI3 AI2 AI1 0: Positive Logic, Enabled at On/Disabled at Off 1: Negative Logic, Disabled at On/Enabled at Off