EM600 High-Performance Vector Control Inverter User Manual 0: Enabled when multi-function input terminal is on, disabled when multi-function input terminal is off; 1: enabled when multi-function input terminal is off, disabled when multi-function input terminal is on; Such function codes are under bit operation. Set corresponding position as 0 or 1 while setting them. Take F02.15 as as example (see the table below): Table 7-5 Function Code of Bit Operation The 7 th bit will not be used. This bit can not be set and the displayed value does not have any meaning. For example: set X1 to negative logic by setting its corresponding bit 0 as 1, i.e., F02.15=xxx xxxx1.
Set X1 and X6 to negative logic by setting corresponding bit 0 of X1 and corresponding bit of X6 as 1, i.e., 02.15=xx1 xxxx1. ★ This function is used for matching with the logic of other peripherals. Sampling clock 1ms Xi input Anti-Interference T he interference is less than the anti-shake filter T he interference is greater than the Note: Assuming that the anti-shake filter times is the default Figure 7-8 Terminal Filter Sampling Because multi-function input terminals adopt level triggered mode or pulse triggered mode, when inverter is reading terminal status, multi-function input terminal signal has to be processed by digital filtering in order to avoid interference.
★ This code does not need to be adjusted on general applications. When an adjustment is required, please note the relations between filter times and lasting time when terminal is on. It is to avoid that inverter is easy to be interfered with due to insufficient filter times, or slow response or command loss due to too many filter times.
times anti-shake filter times value 2 145 Set Item * X7 X6 X5 X4 X3 X2 X1 Corresponding Bit 7 6 5 4 3 2 1 0 Set Value * 0/1 0/1 0/1 0/1 0/1 0/1 0/1 Parameter Function Code Name of Funciton Code Unit Default Property Description F02.17 Numeric input terminal filter times 0 – 100, 0 means no filter, n means nms sampling for 1 time 2 〇 Function Code Name of Function Code Parameter Description Unit Default Property F02.18 X1 Effective Delay Time 0.000 - 30.000 s 0.000 ● F02.19 X1 Ineffective Delay Tim e 0.000 - 30.000 s 0.000 ● F02.20 X2 Effective Delay Time 0.000 - 30.000 s 0.000 ●