EM600 High-Performance Vector Control Inverter User Manual When output type of function output terminal is monopulse output (see F03.05), user can control active level pulse width by setting monopulse output time to meet various process or control requirements. See Figure 7-14 and Figure 7-16 for details. M1 and M2 are 2 multi-function analog output terminals and Y2 can be set as a high-speed pulse output terminal (F03.07=1). By setting function codes F03.21 - F03.23, user can define the functions of output terminals.
For example, if F03.21=0, function of M1 terminal is to output “Running frequency (absolute value)”, and reflects present value of “Running frequency” (absolute value)” by outputting different voltage values. If running frequency increases from 0.00 Hz to 50.00 Hz (assuming F00.16=50.00), then default application is that M1 output voltage increases from 0.00V to 10.00 V, with the same variation trend as that of running frequency. Specific functions available are shown in Table 7-7. Table 7–7 Multi-Function Analog Output Terminals ★ :
Fmax, Maximum Frequency (F00.16) 156 Function Code Name of Function Code Parameter Description Unit Default Property F03.17 Y1 Output Monopulse Time 0.000 - 30.000 s 0.250 ● F03.18 Y2 Output Monopulse Time 0.000 - 30.000 s 0.250 ● F03.19 R1 Output Monopulse Time 0.000 - 30.000 s 0.250 ● F03.20 R2 Output Monopulse Time 0.000 - 30.000 s 0.250 ● Function Name of Function Parameter Description Unit Default Property Code Code F03.21 Analog Output M1 See Table 7–7 Multi-Function Analog Output Terminals 0 〇 F03.22 Analog Output M2 2 〇 F03.23 Y2 High-Frequency Pulse Output Function 11 〇 Set Value Function Description 0 Running frequency (absolute value) 0.00 Hz - Fmax, corresponding output 0.0% - 100.0% 1 Set frequency (absolute value) 0.00 Hz - Fmax, corresponding output 0.0% - 100.0% 2 Output torque (absolute value) 0.0% - 200.0%, corresponding output 0.0% - 100.0% 3 Set torque (absolute value) 0.0% - 200.0%, corresponding output 0.0% - 100.0% 4 Output Current 0.0A - 2*Ie, corresponding output 0.0% - 100.0% 5 Output Voltage 0.0V - 1.5*Ue, corresponding output 0.0% - 100.0% 6 Bus voltage 0V - 1000V, corresponding output 0.0% - 100.0% 7 Output Power 0.00kW - 2*Pe, corresponding output 0.0% - 100.0% 8 AI1 Output actual input voltage, other than results after offset 100.0%, corresponding output 0.0% - 100.0% 9 AI2 10 AI3 11 AI4 (Expansion Card) 12 High-Speed Pulse Input F02.26 - F02.28, corresponding output 0.0% - 100.0% 14 Value of Count 0~F16.03 is corresponding to F16.10~F16.11 15 Value of Length 0~F16.03 is corresponding to F16.10~F16.11