EM600 High-Performance Vector Control Inverter User Manual Before inverter starts, motor can run at low speed or reverse. Starting inverter at this time immediately can result in overcurrent fault. In order to avoid such a fault, add the link of DC brake at first prior to inverter start to stop motor, and then start inverter to set frequency according to set direction. Different values of F04.03 may realize different start DC brake torques. By setting the action time of DC brake through F04.04, inverter starts immediately after set time is out. If F04.04=0.00, DC brake is disabled at start. ★ The process of starting DC brake is shown in Figure 7-18.
This function may be enabled when single inverter serves multiple motors and inverter is starting. Inverter develops a magnetic field as set pre-excitation current, and starts running after set pre-excitation time (F04.07) are out. If set pre-excitation is 0, inverter will start directly without the pre-excitation link. F04.06 pre-excitation current is a percentage relative to motor’s no load current. When starting mode is selected as torque tracking start (F04.00=1), inverter will perform torque tracking as per setting through F04.08 at start. Please select a proper mode according to application, so as to better track present motor running frequency.
This mode can be selected when inverter starts tracking downwards from maximum frequency (F04.08=0) and running status of motor is completely unsure (motor is in rotation status when inverter is powered on). If F04.08=1, it means that inverter starts tracking from stop frequency. Generally, this mode is selected; If F04.08=2, it means that inverter starts tracking from grid frequency. This mode can be selected if grid frequency changes to frequency conversion.
158 Function Name of Function Code Parameter Description Unit Default Property Code F04.03 DC Brake Current at Start 0.0 - 100.0 (100.0= Motor Rated Current) % 100.0 〇 F04.04 DC Brake Time at Start 0.00 - 30.00 s 0.00 〇 F04.05 DC Brake Field Weakening Time at Start 0.00 - 30.00 s 0.50 〇 Function Name of Function Parameter Description Unit Default Property Code Code F04.06 Pre-Excitation Current 50.0 - 500.0 (100.0=Idling Current) % 100.0 〇 F04.07 Pre-Excitation Time 0.00 - 10.00 s 0.10 〇 Function Name of Function Code Parameter Description Unit Default Property Code F04.08 Rotation Speed Tracking Method 0: Start from Maximum Frequency 1: Start from Stop Frequency 2:
Start from Grid Frequency 0 〇