EM600 High-Performance Vector Control Inverter User Manual F04.20 is used to set the frequency of starting DC brake in ramp-to-stop. During ramp-to-stop, once output frequency is lower than this value, inverter will start DC brake if DC brake time at stop is not set as 0. Different values of F04.21 may realize different DC brake torques at stop. F04.22 is used to set action time of DC brake at stop. If F04.22=0.00, DC brake at stop will be disabled. If there is also a signal of DC brake from an external terminal, then DC brake time at stop shall be the bigger of the following two: action time of DC brake signal of external terminal, and time set through F04.22.
For 04.23, inverter starts DC brake in ramp-to-stop when output frequency reaches the value set through F04.20 and the time set by F04.24 is reached. Process of DC brake at stop is shown in Figure 7-19. Output frequency (Hz) Output frequency (Hz) 0 Time(S) Motor speed 0 Time(S) DC brake frequency t DC brake field weakening time Time (S) Brake voltage/current T Brake time Time(S) t Figure 7-18 Start Process of DC Brake Figure 7-19 Stop Process of DC Brake 0 Generally, for a heavy load, deceleration operation may not stop motor completely after deceleration time is out due to inertia; extending DC brake time at stop or increasing DC brake current at stop can stop motor.
When magnetic flux brake is enabled (F04.24>100), inverter can enable motor for rapid deceleration by the method of increasing magnetic flux of motor. At this time, electric energy in motor brake process can be transformed into thermal energy.
Magnetic flux brake can be used to realize rapid deceleration, but output current may be large, user may set magnetic flux brake intensity (F04.24) for limit protection so as to avoid 161 Function Name of Function Code Parameter Description Unit Default Property Code F04.20 DC Brake Start Frequency at Stop 0.00 - Maximum Frequency F00.16 Hz 0.00 〇 F04.21 DC Brake Current at Stop 0.0 - 150.0 (100.0= Motor Rated Current) % 100.0 〇 F04.22 DC Brake Time at Stop 0.00 - 30.00, Disabled at 0.00 s 0.00 〇 F04.23 DC Brake Field Weakening Time at Stop 0.00 - 30.00 s 0.50 〇 Function Name of Parameter Description Unit Default Property Code Function Code F04.24 Magnetic Flux Brake Gain 100 – 150 (100:
No Magnetic Flux Brake) 100 〇