EM600 High-Performance Vector Control Inverter User Manual 7.6 F05 Group: VF Control Parameter This group of function codes is only valid for V/F control and not valid for vector control. V/F control applies to general loads like fan and water pump, or to the occasion “one inverter shared by multiple motors” or the occasion where there is high difference between inverter power and motor power. F05.00=0: Straight Line V/F Applies to general constant torque load F05.00=1: Multi-Pot V/F By setting parameters of F05.01 - F05.06, user may obtain a user-defined V/F curve. F05.00=2/3: VF to the 1.3 rd / VF to the 1.7 th Refers to VF curve that goes between linear VF and square VF. F05.00=4:
Square V/F Applies to centrifugal loads like fan and water pump. F05.00=5: VF Complete Split Mode Inverter output frequency and output voltage are independent, with output frequency determined by frequency source and output voltage determined by F05.07 (Voltage Source of VF Separation Mode). This mode is generally used for occasions such as induction heating, inversion power supply and torque motor control. F05.00=6: VF Complete Split Mode In this mode, V and F are proportional. However, the proportion can be set through power supply source (F05.07) and this proportion has something to do with motor rated voltage and rated frequency of F1 group.
Assuming that power supply source is X (0 - 100%), the relationship between output voltage V and frequency F is as follows: V/F=2*X* (motor rated voltage) / (motor rated frequency) When speed of motor rotor decreases as load increases, user may enable slip compensation so as to ensure that rotor speed is close to synchronous speed under a condition that motor 163 Function Name of Parameter Description Unit Default Property Code Function Code F05.00 V/F Curve Setting 0: Straight V/F 1: Multi-Dot Polyline V/F 2: VF to the 1.3rd 3: VF to the 1.7th 4: Square V/F 5: VF Complete Split Mode (Ud=0, Uq=K*t=Split voltage source voltage) 6:
VF Half-Split Mode (Ud=0, Uq=K*t=F/Fe*2*Split voltage source voltage) 0 〇 Function Name of Function Code Parameter Description Unit Default Property Code F05.11 V/F Slip Compensation Gain 0.00 - 200.00 % 100.00 ● F05.12 V/F Slip Filter Time 0.00 - 10.00 s 1.00 ●