sinee — 7.6 F05 Group: VF Control Parameter

EM600 High-Performance Vector Control Inverter User Manual is under rated load. If motor speed goes below the target value, increase the value set through F05.11. When rotor speed drops by an increase of load, to ensure rotor speed is close to synchronous speed under rated load, slip compensation can be applied, increase setting value of F05.11. ★ If F05.11=0, slip compensation is disabled; this parameter is only enabled for synchronous motor. When inverter makes a quick start under large inertia, the slip is 100%; after reaching set frequency, the slip is 0; quick decrease of output frequency would result in overvoltage or overcurrent. F05.02 may mitigate the boost of voltage and current.

Parameters of function codes F05.05 - F05.10 will be enabled if Multi-Dot Polyline V/F is selected (F05.00=1). A user-defined V/F curve is determined by the curve set with input frequency percentage and output voltage percentage, and it is linearized at different segments in different input ranges. Motor rated frequency is the ultimate frequency reached by V/F curve and also the frequency at maximum voltage output. Input frequency percentage: if motor rated frequency is the input frequency, the percentage is 100.0%; output voltage percentage: if motor rated voltage is output voltage (U e ), the percentage is 100.0%.

The relationship between the three voltage points and the frequency point must meet the following requirements: V1 An excessive slope of V/F curve may result in an “overcurrent” fault. Especially, an excessively high voltage at low frequency may cause motor to be overheated or burn motor and inverter may get in overcurrent stall or overcurrent protection.

164 Function Name of Function Parameter Description Unit Default Property Code Code F05.01 Multipoint VF Frequency Point F1 0.00 - F05.03 Hz 0.50 ● F05.02 Multipoint VF Voltage Point V1 0.0 - 100.0 (100.0= Rated Voltage) % 1.0 ● F05.03 Multipoint VF Frequency Point F2 F05.01 - F05.05 Hz 2.00 ● F05.04 Multipoint VF Voltage Point V2 0.0 - 100.0 % 4.0 ● F05.05 Multipoint VF Frequency Point F3 F05.03 - Motor Rated Frequency (Reference Frequency) Hz 5.00 ● F05.06 Multipoint VF Voltage Point V3 0.0 - 100.0 % 10.0 ●