sinee — 7.6 F05 Group: VF Control Parameter

EM600 High-Performance Vector Control Inverter User Manual Output Voltage (%) Motor Rated Voltage V3 V2 V1 F1 F2 F3 Output Frequency (%) Motor Rated Frequency Figure 7-20 Multi-Dot Polyline V/F Curve VF separation is generally used for occasions such as induction heating, inversion power supply and torque motor control. In VF separation control, output frequency can be set by F05.08 as well as analog quantity, high speed pulse, PID or communication setting. In nonnumeric setting, 100% of each setting refers to motor’s rated voltage. When set percentage of analog output is negative, then take set absolute value as effective value. F05.07=0 :

Numeric Setting of VF Separation Voltage (F05.08) VF separation output voltage is determined by the numeric setting of VF separation voltage (F05.08). F05.07=1: AI1 F05.07=2: AI2 F05.07=3: AI3 F05.07=4: High-Frequency Pulse Input (X7) VF separation output voltage is determined by AI/HDI (percentage) * Numeric Setting of VF Separation Voltage (F05.08). Please refer to the description of F00.04 for detailed explanations of AI1-AI3 and X7. F00.04 has the same meanings as AI1-AI3 and X7. 100.00% is the percentage inputted through F05.08 (Numeric Setting of VF Separation Voltage).

165 Function Name of Function Code Parameter Description Unit Default Property Code F05.07 Voltage Source of VF Separation Mode 0: Numeric Setting of VF Separation Voltage 1: AI1 2: AI2 3: AI3 4: High-Frequency Pulse (X7) 5: PID 6: Communication Setting Note: Motor Rated Voltage is 100%. 0 〇 F05.08 Numeric Setting of VF Separation Voltage 0.0 - 100.0 (100.0=Motor Rated Voltage) % 0.0 ●