sinee — 7.7 F06 Group: Vector Control Parameter

EM600 High-Performance Vector Control Inverter User Manual In VVF, adjusting this parameter can suppress motor oscillation. However, do not adjust it or adjust this parameter to a smaller value properly if there is no motor oscillation; in case of apparent oscillation, adjust this parameter to a bigger parameter properly. This function is usually applied to load distribution when multiple motors bear one load. Inverter output frequency goes down as load increases; when multiple motors bear the same load, motor output frequency for load will decrease more, thus reducing load of motor and realizing the even load of multiple motors.

This parameter refers to the decline of output frequency when inverter is in rated load output. Energy saving rate (F05.16) indicates energy saving capacity. The higher set value is, the better energy saving effect will be. If it is set as 0.00, energy saving is disabled. When energy saving running is enabled, energy saving applications are reached and energy saving actuation time (F05.17) is maintained, then energy saving control will start. These are optimized parameters for VF control of synchronous motor. Generally, user adopts the defaults. 7.7 F06 Group:

Vector Control Parameter 167 Parameter Function Code Name of Function Code Unit Default Property Description F05.13 Oscillation Suppression Gain 0 - 20000 100 ● F05.14 Oscillation Suppression End Frequency 0.00 - 600.00 Hz 55.00 ● Parameter Function Code Name of Function Code Unit Default Property Description F05.15 Sagging Control Frequency 0.00 - 10.00 Hz 0.00 ● Function Name of Function Code Parameter Description Unit Default Property Code F05.16 Energy Saving Rate 0.00 - 50.00 % 0.00 ● F05.17 Energy Saving Actuation Time 1.00 - 60.00 s 5.00 ● Function Parameter Name of Function Code Unit Default Property Code Description F05.18 Compensation Gain of Magnetic Flux of Synchronous Motor 0.00 - 500.00 % 100.00 ● F05.19 Filter Time Constant of Magnetic Flux Compensation of Synchronous Motor 0.00 - 10.00 s 0.50 ● Function Name of Function Code Parameter Description Uni t Default Property Code F06.00 Speed Proportional Gain ASR P1 _ 0.00 - 100.00 12.00 ● F06.01 Speed Integral Time Constant ASR T1 _ 0.000 - 30.000 0.000:

No Integral s 0.200 ● F06.02 Speed Proportional 0.00 - 100.00 8.00 ●